Find a Rep

Contact Us

TV/SC-A Ambient Sensing Steam Tracing Control Valve

The TV/SC-A is a thermostatic steam tracing control valve that regulates heating media for freeze protection, tracing, and enclosure heating applications.

Key Features

Ambient Temperature Sensing – Responds to surrounding air temperature rather than process or pipe surface temperature
Self-Actuating Operation – Requires no external power or electronic controls
Tube-Fitting Integration – Parker A-LOK or Swagelok fittings support quick and easy connection to tracing systems

Steam Tracing and Freeze Protection Control

The TV/SC-A helps protect piping, instrumentation, and enclosure systems from freezing by supplying heat or other compatible media only when needed. The valve can control steam, air, gas, and liquids compatible with Teflon® and stainless steel, providing a versatile solution for temperature-based control.

By reducing unnecessary steam and media flow, the TV/SC-A helps eliminate waste and lower operating costs associated with continuous heating and manual winterization.

For applications that require sensing process or pipe surface temperature instead of ambient conditions, see the TV/US-X Steam Tracing Control Valve with Tube Fittings.

Design Features

  • Exclusive Thermoloid® wax thermal actuator
  • Stainless-steel body, fittings, and plugs
  • Compact, low mass – fast response
  • Corrosion-resistant – long service life
  • Ram-type plug for tight reliable shutoff
  • Wide choice of set points available
  • Large flow coefficient (Cv)
  • Unaffected by pressure variations

Typical Applications

The compact and self-contained TV/SC-A valve can be used in countless of applications including:

  • Steam tracing systems
  • Freeze protection for piping and instrumentation
  • Instrument enclosure temperature control and analyzer shelters
  • Outdoor or exposed process equipment
  • Pneumatically operated antifreeze injection systems

Specifications

  • Sizes: 3⁄8”, ½”
  • Maximum Operating Pressure: 200 PSIG (13.8 bar)
  • Maximum Valve End Temp: 388°F (198°C)
  • Maximum Sensing End Temp: Range 150ºF (83.3ºC) over set point with a limit of 300ºF (149ºC)

Ordering

Part NumberDescription
713 – 0X1000 – XXX3/8” TV/SC-A
714 – 0X1000 – XXX1/2” TV/SC-A

Ordering & Configuration Notes

  1. Full open temperatures “XXX” available: 035°F, 040°F, 050°F, 055°F, 060°F, 065°F, 075°F, 085°F, 090°F, 095°F, 100°F, 105°F, 110°F, 120°F, 125°F, 130°F, 140°F, 150°F, 155°F, 160°F, 170°F, 180°F, 190°F, and 200°F.
    • Closing temperature is typically 10°F above opening temperature.
  2. Standard fittings are Parker A-LOK, but Swagelok are available. The first 0 indicates the fittings.
    • 0 = Parker fittings
    • 1 = Swagelok

How the TV/SC-A Valve Works

The TV/SC-A uses a thermostatic actuator that is thermally isolated from the valve body to sense surrounding air temperature. When ambient temperature falls to the valve’s set point, the valve opens to allow the selected media to flow. As ambient temperature rises, the valve modulates toward the closed position, reducing flow once heat or freeze protection is no longer required.

Related Products

Product Title Industry
TV-US-X TV/US-X Steam Tracing Control Valve with Tube Fittings Industrial
HAT/FP Freeze Protection Valve Industrial, Aerospace & Defense
IC/FP Freeze Protection Valve Industrial
US/S-X Steam Tracing Control Valve Industrial
TV/SC-I Instrument Enclosure Temperature Control Valve Industrial
ITCH Assembly | Instrument & Enclosure Temperature Control System Industrial
TV/SC-A Ambient Sensing Steam Tracing Control Valve Industrial
HAT Fluid Temperature Control Valve Industrial, Aerospace & Defense
TV/HAT Fluid Temperature Control Valve with Tube Fittings Industrial, Aerospace & Defense