Find a Rep

Contact Us

TV/HAT-RA Cooling Fluid Control Valve with Tube Fittings

The TV/HAT-RA family regulates cooling fluid in systems using tube-fitting connections. Standard TV/HAT-RA valves respond to inline temperature, while TV/HAT-RA-LP models use controlled leakage for increased sensitivity to upstream temperature.

Key Features

Tube-Fitting Integration – Parker A-LOK or Swagelok fittings support connection to tubing-based cooling systems
Responsive Temperature Control – Thermal actuator responds directly to changing fluid temperature
Self-Actuating Operation – Requires no external power, sensors, or controls

Cooling Fluid Control Valve Overview

The TV/HAT-RA is a self-actuating fluid temperature control valve that opens as temperature rises to increase cooling flow. It can also function as a thermal relief valve to help prevent overtemperature conditions caused by pump deadheading, low-flow operation, or changing heat loads.

For heating applications that require the valve to open as fluid temperature falls, use the TV/HAT fluid temperature control valve.

Valve Configurations

TV/HAT-RA

Standard configuration for controlling cooling media flow based on inline fluid temperature. 

TV/HAT-RA-LP

Includes a controlled leak port that allows the actuator to sense changing upstream fluid temperature when the valve is otherwise closed. 

Design Features

  • Exclusive Thermoloid® paraffin wax actuator
  • Fully wetted thermal actuator for direct response to fluid temperature 
  • Compact, low-mass design
  • Corrosion-resistant – stainless steel body, fittings, spring, and plug
  • Ram-type plug design for tight, reliable shutoff
  • Operates in any orientation and a narrow temperature band 
  • Wide choice of set points 
  • Unaffected by pressure variations

Typical Applications

Cooling Fluid Control

The TV/HAT-RA can be used as a cooling water control valve to remove heat and help maintain the required operating temperature in:

  • Liquid cooling systems 
  • Water-cooled heat exchangers 
  • Water-cooled compressors 
  • Injection molding equipment 
  • Die-casting equipment 
  • Welding equipment 
  • Electrical equipment 
  • Engines 

Thermostatic Balancing

The TV/HAT-RA-LP can provide thermostatic balancing at the cooling media outlet of individual loads. By modulating flow in response to outlet temperature, the valve adjusts cooling flow at each load as outlet temperature changes. Typical applications include injection, rubber, and plastic molding equipment, die casting, and platen processes.

Specifications

  • Sizes: 3⁄8”, 1⁄2”
  • Maximum Operating Pressure: 150 PSIG (10 bar)
  • Maximum Temperature: Range 150ºF (83.3ºC) over set point with a limit of 300ºF (149ºC)

Ordering

Part NumberDescription
223-100X00-XXX3/8” TV/HAT-RA-SS2
223-110X00-XXX3/8” TV/HAT-RA-SS-SW3
224-100X00-XXX1/2” TV/HAT-RA-SS2
224-110X00-XXX1/2” TV/HAT-RA-SS-SW3
223-102X00-XXX3/8” TV/HAT-RA-LP 1⁄4 GPM
223-112X00-XXX3/8” TV/HAT-RA-LP-SW3 1⁄4 GPM
224-102X00-XXX1/2” TV/HAT-RA-LP 1⁄4 GPM
224-112X00-XXX1/2” TV/HAT-RA-LP-SW3 1⁄4 GPM

Ordering & Configuration Notes

  1. Full open temperatures “XXX” available: 040°F, 045°F, 050°F, 060°F, 070°F, 075°F, 085°F, 095°F, 100°F, 105°F, 110°F, 115°F, 120°F, 125°F, 130°F, 140°F, 150°F, 160°F, 170°F, 175°F, 180°F, 190°F, 200°F, and 210°F
    1. Closing temperature is typically 10°F below the opening temperature.
  2. Standard fittings are Parker A-LOK.
  3. Swagelok fittings replace standard Parker fittings.
  4. Replace singular “X” with 0 for EPDM body seals; 1 for Viton body seals
  5. Seal material compatibility:
    1. EPDM – air, water, steam, ketones, and synthetic hydraulic oils
    2. Viton – air, fuel, oil, gas, petroleum-based hydraulic oils

TV/HAT-RA Valve Installation

For pump thermal relief applications, install the TV/HAT-RA as close to the pump casing as practical to minimize the distance between the valve and the temperature being controlled.

When used as an after-flow controller, the TV/HAT-RA-LP is installed on the cooling water outlet of the equipment.

How the TV/HAT-RA Valve Works

The thermostatic cooling valve uses a thermal actuator to continuously sense the temperature of cooling water, glycol, or other cooling media and regulate flow. Because the valve is reverse-acting, it opens as temperature rises. 

As temperature reaches the TV/HAT-RA operating range, the thermal actuator begins to modulate the valve open. If temperature remains above the set point, the valve continues to open, allowing additional fluid discharge. As the temperature falls, the valve modulates toward the closed position, reducing flow. This continuous modulation helps maintain the required operating temperature as conditions change.

For TV/HAT-RA-LP models, the valve maintains a small amount of controlled leakage while otherwise closed. This flow allows the thermal actuator to sense changing fluid temperature upstream in the system.

Related Products

Product Title Industry
US/S-XR Sample Cooler Temperature Control Valve Industrial
TV-US-X TV/US-XR Sample Cooler Temperature Control Valve with Tube Fittings Industrial
EcoFlow® Water Conserving Seal Support System Industrial
ECONO/HAT-RA Pump Thermal Relief Valve Industrial
HAT/RA-HP High Pressure Thermal Relief Valve Industrial
TV/SC-IR Instrument Enclosure Cooling Control Valve Industrial
HST High Sample Temperature Shutoff Valve Industrial
HAT/RA Cooling Fluid Control Valve Industrial
TV/HAT-RA Cooling Fluid Control Valve with Tube Fittings Industrial